Add to Favorites
Share

12kV Ring Main Unit

  • Description
Product Detail

    XD Baoji Electric Co.,Ltd is one of the leading China 12kv ring main unit manufacturers and suppliers, as a professional company, our factory is able to produce quality 12kV RMU, 12kv ring main unit products at competitive price.

    Product Description
          XGN86-12 series Gas Filling RMU is three-phase A.C 50/60HZ indoor complete distributing equipment with the voltage range 12KV. It is used for secondary power distribution system, such as plant, building, urban rail transit and metro to receive and distribute power.
          The structure of this RMU is metal enclosed, cubical fixed, the gas-filled compartment of the RMU is made of stainless steel by way of laser welding. It can be equipped with load switch, load switch-fuse combination electric equipment, disconnector and circuit breaker. The wrong operation can be avoided due to its function of the ‘FIVE PROVENTION’. It can meet the standard requirments of IEC62271-200?IEC62271-103?IEC62271-105?IEC62271-1?GB3906?GB/T11022?GB3804? GB16926 etc.
          Overall dimension (W×D×H mm):
                350×840×1650(load switch unit, load switch-fuse combination unit).
                440×840×1650(circuit breaker unit).
                500×840×1650(PT unit).
    Features of Product
          Altitude above sea level 2000m and below.
          Current rating up to 630 A/20kA.
          Internal arc classified (IAC):AFLR,20kA/0.5s.
          Equipped with load switch, load switch-fuse combination electric equipment, disconnector and circuit breaker.
          The internal barriers are made up of steel plate, and the loss of service continuity category (LSC) can meet the requirments of LSC2B.
          The e gas-filled compartment is made of stainless steel sheet by way of laser welding, test by the helium leak detection, with good seal.
          Plug-in solid insulation busbar coupler between the cabinets, with simple in switchgear installation and expansion.
    Internal or external cone cable plug with simple and fast installation. 
          On line monitoring of gas density function.
    Technical Parameters

    Item

    Unit

        Data

    load switch unit

    load switch-fuse combination unit

    circuit breaker unit

    Rated voltage

    kV

    12

    Rated current

    A

    630

    125

    630

    Rated frequency

    Hz

    50

    Rated short circuit breaking current

    kA

    /

    31.5

    20

    Rated transfer current

    kA

    /

    1700

    /

    Rated Short-time withstand current

    Main circuit

    kA/4s

    20

    /

    20

    Earthing switch

    kA/2s

    20

    /

    20

    Earthing connect circuit

    kA/2s

    17.4

    /

    17.4

    Rated peak withstand current

    Main circuit

    kA

    50

    /

    50

    Earthing switch

    kA

    50

    /

    50

    Earthing connect circuit

    kA

    43.5

    /

    43.5

    Degree of protection

    Enclosure

    IP4X

    Gas-filled compartment

    IP67

    Rated insulation level

    Rated power-frequency withstand voltage

    kV/1min

    42

    Rated lightning impulse withstand voltage

    kV

    75

    IAC

    Fault current

    kA

    20

    Duration

    s

    0.5

    SF6 gas rated pressure (rel-20?)

    MPa

    0.04

    SF6 gas alarm pressure (rel-20?)

    MPa

    0.02

     